TM- 9-4910-663-34
Table 2-5.  TROUBLESHOOTING (Continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
If coil resistance is not within specified limits, replace relay K5.
Step 6.  Reconnect lead disconnected in step 5.  With circuit breaker switch CB1 set to OFF position, check
for continuity across appropriate terminals (fig 2-4) of POLARITY REVERSING switch S7 with switch
set to NEG GND position.
Replace switch S7 if open indication is obtained.
6.  LOAD BAND CIRCUIT
a.      LOAD   BANK   CIRCUIT   INOPERATIVE   OR   OPERATES   ERRATICALLY   DURING   TESTING   OF   EXTERNAL
COMPONENTS.
Step  1.    Set  all  LOAD  SELECTION  switches  to  OFF  position.    Set  DC  AMMETER  LOAD  &  STARTER
OUTPUT  CURRENT  BATTERY  CHARGE  CURRENT  RANGE  switch  S14  to  LOAD  X1  position.
Connect ohmmeter between REGULATOR B±  and REGULATOR B-binding posts.  Check to see that
circuit   breaker   switch   CB1,   CIRCUIT   BREAKERS   CB2   DRIVE   CONTROL   circuit   breaker,   and
CIRCUIT   BREAKERS   CB5   RELAY   CONTROL   circuit   breaker   are   all   set   to   ON   position.      Set
MASTER LOAD DISCONNECT switch S8 and LOAD SELECTION 0-25 AMPS/0-12.5 AMPS switch
S24 to ON position.  Check ohmmeter indication as VARIABLE LOAD control R32 is rotated from fully
counterclockwise setting to fully clockwise setting.  Resistance should vary between 46.1 ohms ±5%
and 1.14 ohms ±5%.
If ohmmeter indicates open circuit, proceed to step 2; if indication is normal, proceed directly to step
9.
Step 2.  Using ohmmeter, check for 1.14 ohm ±5% indication between REGULATOR B-binding post and load
bank terminal 19.
If resistance is not as specified, replace load bank element.
Step 3.  Using ohmmeter, check resistance between center terminal of rheostat R32 and terminal with lead.
Resistance should be variable between 0 and 45 ohms.
2-26